Heat Pump COP from Capacity & Power
A heat pump's efficiency is not one number — it changes with the outdoor temperature. Enter the heat output (BTU/h) and electrical input (watts) from the unit's performance data at a temperature and get the COP at that point, the coefficient of performance that says how many units of heat you get per unit of electricity.
Calculator
Delivering 36,000 BTU/h for 3,517 W is a COP of 3.00 at that outdoor temperature (COP = BTU/h ÷ (W × 3.412)).
The coefficient of performance (COP) is the cleanest way to describe a heat pump: it is simply the heat delivered divided by the electricity consumed, both in the same energy units. A COP of 3 means three units of heat into the house for every unit of electricity drawn — roughly 300% "efficient" compared with the 100% ceiling of resistance heat. Unlike the seasonal HSPF2 rating, COP is a point value: manufacturers publish it (or the capacity and power it is derived from) at several outdoor temperatures, because both the heat a unit can make and the power it draws shift as it gets colder. This tool turns a capacity and a power draw into the COP at that operating point.
Formula
Convert the electrical input to the same units as the heat output, then divide:
COP = heat output (BTU/h) ÷ (power (W) × 3.412)
The factor 3.412 converts watts to BTU/h (1 W = 3.412 BTU/h), so both quantities are in BTU/h and the COP is a pure, unitless ratio. Higher is better: more heat delivered for the same power means a lower running cost.
Worked example
Suppose the performance table lists 36,000 BTU/h of heat output for a 3,517 W draw at a given outdoor temperature:
COP = 36,000 ÷ (3,517 × 3.412) = 36,000 ÷ 12,000 = 3.0
So the unit is running at COP 3.0 at that temperature — it delivers three times as much heat as the electricity it consumes. Read the capacity and power at a colder temperature and the COP will be lower; do it at a mild temperature and it will be higher. Collect a few points this way and you can see the whole efficiency curve, then feed the relevant COP into the balance-point and running-cost tools.
Where to find the numbers
Manufacturers usually publish "expanded performance data" or a submittal sheet with capacity (BTU/h) and power (kW or W) at outdoor temperatures like 47°F, 35°F, 17°F and 5°F. Enter the pair for the temperature you care about — watts, not kilowatts (multiply kW by 1,000). If the sheet lists total power in kW, a 3.517 kW draw is 3,517 W. The result is the steady-state COP and does not include defrost penalties or cycling losses, so a real seasonal average will be a bit lower than the best point values.
COP and HSPF2 measure related things: COP is an instantaneous ratio, while HSPF2 is a seasonal figure in BTU per watt-hour. A rough conversion is HSPF2 ≈ COP × 3.412; the COP ↔ HSPF2 converter makes that explicit. Use COP for point-by-point comparisons and HSPF2 for whole-season estimates.