ASHRAE 62.2 ventilation rates

ASHRAE Standard 62.2 asks for two things, and a dwelling has to meet both to comply: a continuous whole-house mechanical ventilation rate, set at 0.03 × floor area + 7.5 × (bedrooms + 1) CFM, and separate local exhaust in the kitchen and in each bathroom. The first table below gives the whole-house rate for common home sizes — compute yours with the ventilation-CFM tool; the second gives the local-exhaust rates. Local fans do not count toward the whole-house rate, and the whole-house fan does not count toward local exhaust.

Whole-house ventilation

Floor areaBedroomsRequired CFM
1,000 sq ft253 CFM
1,500 sq ft375 CFM
2,000 sq ft390 CFM
2,500 sq ft4113 CFM
3,000 sq ft4128 CFM

ASHRAE 62.2: CFM = 0.03 × floor area + 7.5 × (bedrooms + 1). Continuous whole-house mechanical ventilation, delivered by one fan, a balanced HRV/ERV or a central-fan-integrated supply — the standard sets the rate, not the equipment.

Local exhaust

RoomIntermittent fanContinuous fan
Bathroom (each)50 CFM20 CFM
Kitchen (range hood, vented outdoors)100 CFM—

Local exhaust is additional to the whole-house rate above: a 2,000 sq ft, 3-bedroom home needs 90 CFM of continuous whole-house ventilation and a vented range hood and a fan in every bathroom. A fan rated for a figure in this table rarely moves it once ducting, elbows and a grille are added, so verify installed airflow with a flow hood rather than trusting the box.

The continuous kitchen option is not stated as a fixed CFM here; use an intermittent vented range hood, or check the edition of the standard in force in your jurisdiction. Figures are the typical values also published on the ventilation-CFM tool — confirm against your local code, which may amend them.